17

2022

01

When installing and operating an electric control valve, please observe the following points:


Installation and Usage Electric control valve Pay attention to the following points.
1. Control valves are field instruments and require an ambient temperature range of –25 to 60°C, with relative humidity ≤ 95%. If installed outdoors or in high-temperature environments, appropriate waterproofing and cooling measures must be implemented. Keep the valve away from vibration sources, or install additional vibration‑damping measures in areas where vibrations are present.
2. Control valves should generally be installed vertically; in special cases, they may be installed at an angle. If the tilt angle is excessive or the valve’s own weight is too great, additional supports shall be provided to safeguard the valve.
3. In general, the distance between the pipeline where a control valve is installed and the ground or floor should not be excessively high. When the pipeline height exceeds 2 meters, a platform should be provided whenever possible to facilitate operation and maintenance of the handwheel.
4. Prior to installing the control valve, the piping shall be cleaned to remove dirt and welding slag. After installation, to ensure that no foreign matter remains inside the valve body, the valve should be flushed again by opening all valves while the process medium is flowing, thereby preventing debris from becoming lodged. Following use of the handwheel mechanism, it must be returned to its original neutral position.
5. To ensure continued operation of the process in the event of a control valve failure or during maintenance, a bypass line should be installed. Additionally, special attention should be paid to ensuring that the control valve’s installation location meets the process requirements.
6. The electrical installation of electric control valves shall be carried out in accordance with the relevant construction requirements for electrical equipment.
7. After disassembling and overhauling the actuator’s reducer, be sure to lubricate it with fresh oil; low-speed motors generally should not be disassembled for cleaning or greasing. Following assembly, verify that the valve position matches the indicated valve opening.