The meanings represented by actuator devices with different protection levels on valve actuators.
Switch‑type valve electric actuators are generally categorized into standard on/off actuators and integral on/off actuators. They typically provide full‑open or full‑close control, with the valve either fully open or fully closed; such valves do not require precise media flow regulation.
Depending on the structural design, switch‑type valve actuators can be classified as either split‑type or integral‑type—commonly referred to as standard switch‑type valve actuators and integral switch‑type valve actuators. When selecting an actuator, it is essential to clearly specify its type; otherwise, mismatches such as conflicts with the control system during installation are likely to occur.
Split structure (commonly referred to as the ordinary structure):
The control console and the valve actuator are separate; the valve actuator alone cannot independently control the valve and requires an external control unit to perform this function. Typically, such systems are integrated with an external controller, a control cabinet, or a control box.
The drawbacks of this architecture are that it complicates system installation, increases wiring and installation costs, and is prone to failures. Moreover, when malfunctions occur, diagnosis and repair become cumbersome, resulting in poor cost-effectiveness.
Integrated structure (often referred to as a holistic structure):
The control unit of the present invention is integrated with the valve actuator, enabling local operation without an external control unit; remote operation can be achieved simply by transmitting the corresponding control signals.
This structure facilitates the overall installation of the system, reduces wiring and installation costs, and simplifies diagnostics and troubleshooting. However, traditional integrated‑structure products also suffer from numerous drawbacks, which has led to the development of intelligent valve‑actuator devices.
Protection rating is one of several key parameters for valve electric actuator devices, and its applications and costs vary depending on the specific rating. Generally, protection ratings are denoted by IP followed by two digits; the second pair of digits indicates the level of protection. But what do these numbers signify, and how do the different protection ratings differ from one another?
The first digit indicates the level of protection against exposure and external objects (protection rating).
0——Unprotected.
1- Protects against solid foreign objects with a diameter of 50 mm or greater.
2- Protection against solid objects with a diameter of 12.5 mm or greater.
3-Protects against external forces acting on solid objects with a diameter of 2.5 mm or greater.
4-Protects against solid foreign objects with a diameter of 1.0 mm or greater.
5- Dust protection cannot completely prevent dust from entering, but the amount of dust that does enter will not damage the equipment.
6- Fully enclosed to prevent the ingress of external objects and completely block dust from entering.
The second digit indicates the level of water resistance (protection).
0——Unprotected.
1- Protection: Water droplets falling vertically should not cause damage.
2- The drip-proof cabinet shall be tilted at an angle of 15 degrees in any direction; vertically falling water droplets will not cause damage.
3- Water sprayed from the protective nozzle shall not cause damage when discharged within a 60-degree angle on either side of the vertical.
4- Protection against water splashes from any direction; no damage shall result.
5- Protection: Water sprayed from nozzles directed at the enclosure from any direction shall not cause damage.
6- Protection against powerful water jets: Powerful water jets directed at the cabinet from any direction shall not cause damage.
7- Protection against brief immersion in water at standard pressure, ensuring no damage occurs due to water ingress.
8- Long‑duration immersion protection allows the device to be submerged in water under specific conditions, ensuring it will not be damaged by water ingress.