13
2022
06
Gain a comprehensive understanding of the operating procedures and maintenance of valve actuators.
Electric valve actuator The operating method.
I. Preparations Before Operation.
1.1 Before operating the valve, carefully read the operating instructions.
1.2 Before operation, the gas flow direction must be clearly identified, and the valve open/close indicators should be carefully checked.
1.3 Inspect the exterior of the electric valve to determine whether it is damp. If damp, it should be dried; if any other issues are detected, they should be addressed promptly to ensure trouble-free operation.
1.4 For electrical equipment that has been out of service for more than three months, before restarting, inspect the clutch to confirm that the handle is in the manual position, and then check the motor’s insulation, rotation direction, and electrical circuit.
II. Precautions for Operating Electric Valves.
2.1 Before starting, ensure the clutch lever is in the correct position.
2.2 If the electric valve is controlled from the control room, set the transfer switch to the REMOTE position, and then operate the electric valve via the SCADA system.
2.3 If operating manually, set the transfer switch to the LOCAL position and operate the electric valve locally. When the electric valve reaches its fully open or fully closed position, it will automatically stop; then return the transfer switch to the middle position.
2.4 When operating valves on-site, monitor the valve’s open/close indication and stem movement; the valve opening and closing degrees shall comply with the specified requirements.
2.5 When the valve is fully closed on site, electric actuation of the valve shall be stopped before it reaches the fully closed position, and the valve shall be closed using a micro‑stroke mechanism.
2.6 When the stroke and overtorque controllers fully open or close the valve, careful monitoring of the stroke is required. If the valve fails to stop at its fully open or fully closed position, an immediate manual emergency stop must be initiated.
2.7 When opening or closing the valve, if the signal indicator light malfunctions, stop immediately and perform an inspection. If the valve emits abnormal noise, stop operation promptly and conduct a thorough check.
2.8 After the operation is successful, the power supply to the electric valve shall be switched off.
2.9 When operating multiple valves simultaneously, attention shall be paid to the sequence of operations to meet process requirements.
2.10 When opening a large-diameter valve equipped with a bypass valve, if there is a significant pressure differential between the two ends, first open the bypass valve to equalize the pressure, then open the main valve; after the main valve is opened, immediately close the bypass valve.
2.11 When receiving or dispatching pig(s) (or pigging devices), the ball valves through which they pass must be fully open.
2.12 Operating ball valves, gate valves, globe valves, and butterfly valves: they must be fully open or fully closed; adjustment is strictly prohibited.
2.13 Operating gate valves. When globe valves and knife‑gate valves are fully closed or fully open, they should be turned an additional 1/2 to 1 full turn.
Maintenance of electric valve actuators.
1. Electric valves shall be stored in a dry, well-ventilated indoor environment, with both ends of the passage sealed.
2. Electric valves stored for extended periods should be inspected regularly, cleaned of dirt, and coated with anti-rust oil on their machined surfaces.
3. After installation, the following key inspection items should be checked regularly:
(1) Seal face wear.
(2) Wear of the trapezoidal threads on the valve stem and valve stem nut.
(3) Determine whether the packing has become obsolete or ineffective; if damaged, replace it promptly.
(4) After maintenance and reassembly, the electric valve shall undergo a sealing performance test.
Operating electric valves shall be neat and intact. Flange threads and bolts on the mounting brackets are essential; threads must be undamaged and free from looseness. If the locknut on the handwheel is found to be loose, it should be tightened promptly to prevent wear at the connection or loss of the handwheel and nameplate. Should the handwheel be lost, it must not be replaced with an adjustable wrench; a matching replacement should be provided without delay. The packing gland cover must not be bent or lack proper pre‑tightening clearance. For electric valves susceptible to contamination by rain, snow, dust, sand, and other debris, a protective shroud should be installed over the valve stem. The scale markings on the electric valve must remain complete, accurate, and legible. Lead seals, caps, and pneumatic accessories on the electric valve must be intact and undamaged. Insulating sleeves must be free of dents and cracks.
Striking energized electric valves is prohibited. Do not stand on or support heavy objects, especially non-metallic and cast-iron electric valves.