Precautions for the Installation and Operation of Electric Control Valves


Electric control valve It is a common type of control valve, widely used as an end‑control device. In modern industrial automation, it plays a crucial role. Proper operation can significantly extend the service life of electric control valves. Below, we will outline the key considerations for installation and use.
Proper use and maintenance of electric control valves not only enhance the stability of process control but also extend the service life of the valves, delivering significant economic benefits in terms of energy savings and reduced consumption for enterprises. In many cases, on-site malfunctions are attributable not to the valve’s intrinsic quality, but to improper installation.
1. Control valves are field instruments; the ambient temperature range is –25 to 60°C, with a relative humidity not exceeding 95%. In outdoor or high-temperature environments, waterproofing and cooling measures must be implemented. The valve should be installed away from vibration sources, or vibration‑isolating measures should be provided.
2. The regulator should generally be installed vertically; in special circumstances, it may be mounted at an angle—for example, when the valve body itself is excessively heavy, to provide additional support and protection.
3. In general, pipelines equipped with regulators should not be positioned too close to or too far above the ground. When the pipeline height exceeds 2 meters, a platform should be provided whenever possible to facilitate operation of the handwheel and ease maintenance.
4. Before installing the regulator, the pipeline should be cleaned to remove dirt and welding slag. After installation, to ensure that no foreign matter remains inside the valve, the valve should be flushed again; specifically, all valves should be opened when the process medium is introduced to prevent blockage by contaminants. Following use of the handwheel mechanism, the neutral position should be restored.
5. To ensure continuous production during troubleshooting or maintenance, the regulator should be equipped with a bypass line, and special attention should be paid to verifying that its installation location complies with process requirements.
6. The electrical components of the electric control valve shall be installed in accordance with the relevant construction requirements for electrical equipment. For explosion-proof products, installation must comply with the provisions of the “Code for Installation of Electrical Equipment in Explosive Hazardous Locations.” On-site wiring shall use SBH or other six‑core, eight‑core rubber‑sheathed cables with a diameter of Φ11.3 mm. During operation and maintenance, it is prohibited to open the enclosure or pry open the explosion‑proof surface in explosive environments. Furthermore, during disassembly and reassembly, the explosion‑proof surface must not be struck or otherwise damaged; after maintenance, the equipment shall be restored to its original explosion‑proof condition.
7. After dismantling the actuator’s reducer, be sure to lubricate it with oil. Generally, low-speed motors are not disassembled, cleaned, or relubricated. Once the valve positioner is installed, verify that the valve position matches the indicated opening degree.