What are the installation requirements for electric control valves?
Electric control valve It is an essential actuating unit in industrial automation process control. As the level of automation in industry continues to rise, it is increasingly deployed across a wide range of manufacturing sectors. Compared with conventional pneumatic control valves, it offers distinct advantages, including energy efficiency—consuming electrical power only during operation—environmental friendliness—zero carbon emissions—and rapid, convenient installation—eliminating the need for complex pneumatic piping and dedicated air‑pump stations. It is primarily used in industrial automation systems for power generation, chemical processing, metallurgy, environmental protection, water treatment, light industry, and building materials, among other fields.
What are its installation requirements?
1. The installation location shall comply with the process flow design requirements and be positioned close to the relevant indicating instruments, facilitating manual observation of the instruments via the bypass valve.
2. It shall be installed on the ground or on a platform to facilitate operation and maintenance;
3. Horizontal pipelines shall be installed vertically; in special cases, they may be installed horizontally or at an incline, but must be provided with supports.
4. During facade installation, the valve should be mounted below the bypass. For control valves with a nominal diameter less than 255 mm, they may also be installed above the bypass.
5. The clear vertical clearance from the bottom to the floor or platform surface shall be no less than 400 mm. For single- and double-seat control valves with a reverse‑mounted valve plug, sufficient space must be provided beneath the valve body to allow removal of the valve plug.
6. The clearance at the top of the valve bonnet shall be no less than 2 mm. When the electric control valve and the bypass valve are arranged vertically, they shall be staggered.
7. Shut-off valves shall be gate valves, and bypass valves shall be globe valves; however, when the nominal diameter of a bypass valve exceeds 150 mm, a gate valve may be used. The two shut-off valves and the control valve shall not be arranged in a straight line.
8. A drain valve shall be installed at the low point of the pipeline between the inlet side and the upstream isolation valve of the control valve; a gate valve may be selected for the drain valve.
9. On pipelines containing solid particles, the control valve shall be arranged on the same plane as the bypass valve, or the bypass valve shall be installed below the control valve.
10. At low temperatures, the electric control valve installed on a high-temperature pipeline shall be supported by both a fixed support and a sliding support.
11. It shall be installed in an environment where the temperature does not exceed 600°C and does not fall below -40°C, and away from vibration sources.
12. Pay attention to whether the process has any special requirements regarding the position of the electric control valve.