What are the characteristics of electric valve actuators, and how should they be selected?


With advances in science and technology, traditional valves have been supplemented by electrically driven valve actuators, replacing manual operation. These electrical devices enable convenient opening, closing, and control of valves, representing a significant step forward in technological progress. Valve actuators are indispensable for implementing programmed, automated, and remote control of valves. Their motion can be regulated by stroke, torque, or axial thrust. The performance and utilization efficiency of valve actuators depend on the valve type, the system in which they operate, and the valve’s location within the pipeline or equipment.
I. What are the characteristics of electric valve actuators?
Electric actuation is a common method of valve operation, typically referred to as an electric valve actuator. The characteristics of electric valve actuators are as follows:
1. Rapid opening and closing can significantly reduce the time required to operate the valve.
2. It can significantly reduce the physical workload of operators and is particularly well-suited for high-pressure, large-diameter valves.
3. Suitable for installation in locations that cannot be manually controlled or are difficult to access, enabling long-distance operation and unrestricted mounting height.
4. It facilitates the automation of the entire system;
5. Power supplies are easier to obtain than gas or fluid sources, and their wiring is much simpler to install and maintain than compressed-air or hydraulic pipelines.
II. How to Select Electric Actuators for Valves Correctly?
1. Operating torque
Operating torque is the most fundamental parameter for selecting an electric actuator for a valve. The output torque of the actuator should be 1.2 to 1.5 times the valve’s maximum operating torque.
2. Operating Thrust
There are two main structural types of valve electrical actuators: one directly transmits torque without a thrust disc, and the other uses a thrust disc to transmit torque via a stem nut housed within the thrust disc.
The number of revolutions of the output shaft of an electric actuator is determined by the valve’s nominal pipe diameter, the stem thread pitch, and the number of threads on the stem; it should be calculated as M = H/ZS, where M represents the total number of revolutions required for the actuator, H is the valve opening stroke, S is the stem thread pitch, and Z is the number of threads on the stem.
If the maximum allowable stem diameter of the electric actuator cannot pass through the valve stem of the equipped valve, the assembly cannot be configured as an electric gate valve. Therefore, the inner diameter of the hollow output shaft of the electric actuator must exceed the stem diameter of the open‑stem valve. For open‑stem valves used in quarter‑turn and multi‑turn actuators, although passage of the stem diameter is not a concern, the stem diameter and the dimensions of the pin holes should still be carefully considered to ensure proper operation after assembly.
3. Export rotational speed
If the valve is opened or closed too quickly, water hammer can easily occur. Therefore, the appropriate opening and closing speed should be selected based on the specific operating conditions.