27
2022
10
Soupai Shi introduces the commissioning procedures for electric actuators.
For the production processes of many enterprises, ensuring… Electric actuator Ensuring its normal operation is of utmost importance. During this process, any issues that arise can significantly impact us. In most cases, our primary focus is on extending the equipment’s service life. To achieve this, we employ various measures, such as controlling dust and moisture in the operating environment or applying surface treatments to the components. In fact, there is another critical aspect: proper equipment alignment and effective troubleshooting procedures.
The basic adjustment procedures and troubleshooting for electric actuators can be carried out using the corresponding operation manuals; however, during actual operation, a variety of issues may arise—problems whose solutions are not covered in the manuals. The following section analyzes several common difficulties and malfunctions frequently encountered during the adjustment process.
1. During adjustment, if the ratio of the signal gear module is incorrect, the screen will display “increase it” or “decrease it” after the switch is positioned. After setting the limit switch, toggling the S7 DIP switch once—switching it from ON to OFF and back—will cause the green light to flash once per second while the red light remains steadily on, which can prevent the end‑position setting from succeeding.
Solution: Before initiating the adjustment procedure, first calculate the module ratio for the signal gear and select the nearest available gear based on this calculation. Then, verify the initial position of the intermediate gear prior to starting the final adjustment. Typically, the symbols “1” and “2” on the intermediate gear are oriented toward the 11 o’clock and 1 o’clock positions, respectively; adjustments should be performed in accordance with the instructions provided in the manual.
2. The operation failed because the tail position was initially set to the OFF position.
Solution: The manual does not specify requirements for setting the start‑end position; however, in practice, it has been found that you can either set the start‑end position first and then the close‑end position, or alternatively, set the open‑end or close‑end position first.
3. Remote control: No response on-site. Use the setting device to check; fault messages indicate: “H1 torque switch tripped” and “H6 no electromagnetic feedback.”
Solution: The solid-state relay is not outputting. Replace the relay control board or the power supply board component.
4. Manual operation is normal, but electric mode cannot be switched; alternatively, during electric operation, the motor vibrates, stalls intermittently, and its speed slows down.
Solution: The manual clutch‑holding spring is stuck in the manual position. Remove the handwheel, release the holding spring, and reassemble. If the clutch assembly is damaged, it can be replaced later. If the manual clutch is functioning properly, replace the (solid‑state) relay before proceeding with further inspection.
5. After the main circuit power is restored following a power outage, the actuator fails to respond to remote control or local operation, and a low‑battery voltage alarm is triggered.
Solution: Verify that the battery voltage is indeed too low. When the main power is lost and the battery is depleted, the configured settings will be lost. Replace the battery and reset the settings.
6. Unable to enter adjustment mode
Solution: Verify whether the operating procedure is correct or check for a malfunction in the control panel. If the control panel is faulty, it is typically replaced in its entirety.