What are the issues with the control of electric actuators?
Electric actuator After a period of use, it is sometimes observed that the control accuracy of an electric actuator declines compared to its initial performance, necessitating identification of the factors affecting this precision. Based on years of experience, several key causes and corresponding solutions have been distilled. In what follows, we will discuss these in detail.
1. Control valve oscillation. First, identify the source of vibration. For externally induced vibrations, position the control valve away from the vibration source and either eliminate or reduce the vibration amplitude. It may also be appropriate to employ measures such as adding support points to minimize valve oscillation. When oscillation is caused by internal fluid flow, strive to minimize flow resistance across the valve. Under conditions permitted by operational experience, a bypass line can be installed. For systems requiring rapid response and damping, consider using a valve plug with a specially designed logarithmic characteristic. For butterfly valves, operate within the 10°–70° range whenever possible, avoiding the region where alternating forces on the valve body are most pronounced.
2. The electric actuator’s brake is not functioning. The brake is designed to counteract the rotor and output shaft’s inertial coasting, as well as the effects of load‑induced back‑torque, when power is lost, ensuring that the output shaft comes to a precise stop at the desired position. If the brake fails, the braking accuracy of the electric actuator will be compromised. Therefore, the following measures should be taken:
(1) Adjust the braking torque according to the load.
(2) Adjust the clearance between the brake wheel and the brake disc as appropriate.
(3) Brake shoes must maintain an adequate coefficient of friction; the application of oil or other lubricants is prohibited (when adding lubricant, do not exceed the maximum level indicated on the oil dipstick).
3. The output of the electric actuator includes a lagging element. This lag is primarily located at the connection between the output shaft of the angular‑stroke electric actuator and the control mechanism (such as a butterfly valve). Consequently, all linkages and levers must be installed without any looseness or gaps. Whenever possible, use a dedicated coupling to replace the linkage assembly. Our plant’s coke oven gas‑collection‑main pressure‑control system employs such a specialized coupling, with highly satisfactory results. When fabricating the coupling, it is essential to consider the actual installation conditions and ensure that the electric actuator’s 0–90° rotation, the valve body’s 0–90° rotation, and the valve‑position feedback signal of 4–20 mA are properly aligned.