Working Principle of Electric Control Valve Selection
Electric control valve Selection of the operating environment:
When selecting a control valve, the type of valve bonnet and the packing material should also be taken into account. For service temperatures ranging from –20°C to +250°C, a standard design is sufficient; for temperatures between –50°C and +450°C, a heat‑dissipating bonnet with multiple fins is recommended. Additionally, bellows‑sealed bonnets are primarily used in applications involving highly toxic, volatile, or penetrating media.
Selection of sealing packing for electric control valves:
Common sealing packings for control valves include polytetrafluoroethylene and asbestos rope packing; although the former is more expensive than the latter, it provides significantly better sealing performance.
Valve Sizing and Selection Guidelines:
The selection of air‑to‑open or air‑to‑close control valves should be based on the degree of potential harm to the process if the pneumatic signal pressure is interrupted, depending on whether the valve would open or close under such conditions. If a failure to close would result in less severe consequences, an air‑to‑close valve is chosen; its operating sequence is: closed when pressurized, open when de‑pressurized. Conversely, if a failure to open would be less hazardous, an air‑to‑open valve is selected; its operating sequence is: open when pressurized, closed when de‑pressurized.