07
2022
08
What should be considered when installing and using electric control valves?
1. Electric control valve It is a field instrument that requires an ambient temperature range of –25 to 60°C and a relative humidity ≤95%. When installed outdoors or in high‑temperature environments, waterproofing and cooling measures must be implemented. Keep it away from vibration sources or install additional vibration‑damping measures.
2. Electric control valves should generally be installed vertically; in special cases, they may be installed at an angle. If the tilt angle is significant or the valve itself is excessively heavy, additional support or protection for the valve shall be provided.
3. In general, the piping where a control valve is installed should not be too high above the ground or floor; the pipe height should exceed 2 meters. To facilitate operation of the handwheel and maintenance, a platform should be provided whenever possible.
4. Before installing the control valve, clean the pipeline to remove dirt and welding slag. After installation, to ensure that no foreign matter remains inside the valve body, the valve should be flushed again—open the valve when the process medium is introduced—to prevent blockage by contaminants. Following use of the handwheel mechanism, return it to its original neutral position.
5. To ensure that the control valve can maintain the production process in the event of a failure or during maintenance, a bypass line should be installed, and special attention should be paid to verifying that the valve’s installation location complies with process requirements.
6. The electrical components of the electric control valve shall be installed in accordance with the relevant construction requirements for electrical equipment. Explosion-proof products must be installed in compliance with the “Code for Installation of Electrical Equipment in Explosive Hazardous Areas.” If SBH‑type cables or other six‑core or eight‑core cables with an outer diameter of Φ11.3 mm are used, they shall be routed through rubber sleeves on both sides. During operation and maintenance, it is strictly prohibited to energize the equipment in explosive environments, to open the enclosure for maintenance, or to pry open the explosion‑proof surfaces. Furthermore, during disassembly and reassembly, the explosion‑proof surfaces must not be scratched or damaged. After maintenance, the equipment must be restored to its original explosion‑proof condition.
7. After disassembling and overhauling the actuator’s reducer, be sure to lubricate it with fresh oil; generally, do not disassemble or clean the low-speed motor when adding lubricant. Following assembly, verify that the valve position matches the position‑indication scale.